DC Arc Flash Study: Data Collection Checklist
The calculator for this page is switched off while it is checked. The formula is below, and the worked example in the article shows how to use it by hand.
A DC arc flash study calculates the incident energy and arc flash boundary for direct-current systems, and it requires a specific set of system data to produce accurate results. This article provides a practical data collection checklist covering equipment, configuration, and operational details needed for a DC arc flash analysis.
Formula
The incident energy at a given distance is estimated by:
E = (0.01 × V × I × T) / D²
Where:
- E = incident energy (cal/cm²)
- V = system voltage (volts)
- I = fault current (kA)
- T = arc duration (seconds)
- D = distance from the arc (mm)
This simplified model assumes a point source and does not account for electrode configuration or enclosure size. For a real study, use IEEE 1584 or the Lee method for DC as appropriate.
Worked Example
Using the default values: V=500 V, I=10 kA, T=0.2 s, D=455 mm.
E = (0.01 × 500 × 10 × 0.2) / (455²) = 10 / 207025 = 0.0000483 cal/cm², which rounds to 0.00 cal/cm². This shows that at a typical working distance, the incident energy is negligible for these parameters.
Why DC Arc Flash Studies Differ from AC
DC arc flash behavior is not the same as AC. In AC systems, the current naturally passes through zero every half-cycle, which helps extinguish the arc. DC has no zero-crossing, so the arc is more stable and can sustain longer, leading to higher incident energy for the same clearing time. Also, DC fault current is often limited by the source (batteries, rectifiers, PV arrays) and by cable resistance, so the available fault current is not simply the source short-circuit current. This means you need accurate source characteristics and cable data to calculate the actual arc current.
Essential Data for a DC Arc Flash Study
To perform a DC arc flash study, you need the following categories of data:
- System configuration: one-line diagram, voltage levels, grounding method (solid, resistance, ungrounded), and the location of each bus or panel.
- Source data: for each DC source (battery bank, rectifier, PV array, DC generator), collect the open-circuit voltage, short-circuit current, and internal resistance or impedance. For batteries, note the number of cells, cell voltage, and state of charge.
- Conductor data: for every cable and busbar, record the length, cross-sectional area (AWG or mm²), and material (copper or aluminum). This is critical because DC fault current is limited by resistance.
- Protective device data: for each fuse, circuit breaker, or relay, note the type, manufacturer, model, and time-current curve (TCC). Also record the instantaneous and time-delay settings for adjustable devices.
- Arc duration: this is the time for the protective device to clear the fault. It includes the device operating time plus any upstream breaker opening time. For battery systems, consider the maximum fault duration before the source is disconnected.
- Working distances: typical working distance for each piece of equipment (e.g., 455 mm for panelboard, 610 mm for switchgear).
- Enclosure dimensions: the size of the enclosure or whether the arc is in open air. This affects the arc voltage and energy.
- Maintenance and switching procedures: if there are any conditions that increase the arc duration (e.g., delayed tripping during maintenance), note them.
Where to Find the Data
Most of this information is available from existing documentation:
- One-line diagrams show the configuration and device locations.
- Equipment nameplates list voltage, current ratings, and sometimes impedance.
- Battery data sheets provide discharge curves and internal resistance.
- Protective device time-current curves are available from manufacturers or in relay settings files.
- Cable schedules list conductor sizes and lengths.
If documents are missing, you may need to physically inspect the equipment and measure cable lengths. For older installations, verify that the data matches the actual installed equipment.
Common Challenges and How to Overcome Them
One common challenge is missing or inaccurate source data. For example, a battery bank’s short-circuit current may not be listed on the nameplate; you may need to contact the manufacturer or use a battery discharge curve. Another challenge is determining the arc duration when multiple protective devices are involved. You must coordinate the time-current curves to find the total clearing time. Also, DC arc flash calculations are less standardized than AC; use a recognized method such as the Maximo or Stokes method, and state your assumptions clearly.
Frequently Asked Questions
Q: Can I use the same data as an AC study?
No. DC systems have different fault characteristics and require specific source and conductor data. AC studies often ignore resistance because inductance dominates, but in DC, resistance is the main limiter.
Q: What if I don’t know the exact cable length?
Use a conservative estimate (longer length gives lower fault current, but also lower incident energy? Actually, higher resistance reduces current, which reduces energy, but it also slows the protective device, increasing duration. You need both to calculate correctly).
Q: How do I get the arc duration?
It is the time for the protective device to clear the fault, found from the TCC. For battery systems, also consider the maximum time the battery can sustain a fault before voltage collapses.
Q: Is there a simplified formula for DC arc flash?
Yes, the Lee method for DC is often used: E = 0.01 × V × I_arc × T / D², but you need to estimate the arc current, which is typically lower than the bolted fault current. Use an arc current model like the one in the NESC or from research papers.
Q: Do I need to include all DC sources?
Yes, every source that can feed a fault must be considered. For PV systems, include the array and any battery storage. For substations, include the battery bank and any DC chargers.
Q: What if the protective device is not adjustable?
Then use the manufacturer’s published clearing time at the calculated fault current. If you cannot obtain the TCC, use a conservative estimate (e.g., 0.1 seconds for a fuse, 0.05 seconds for a molded case breaker).
Related
Formula used
in t | Time (seconds) | s | 0.2 | 0 in i | Fault current (kA) | kA | 10 | 0 in v | System voltage (V) | V | 500 | 0 in d | Distance from arc (mm) | mm | 455 | 0 out e | Incident energy (cal/cm²) | cal/cm² | (0.01 * v * i * t) / (d^2) * 1000 | 2 out b | Arc flash boundary (mm) | mm | sqrt((0.01 * v * i * t) / 1.2 * 1000) | 0