Ohms to Temp Conversion: What It Really Means

Updated · Standard formula, shown below

RTD temperature (PT100/PT1000) 0.0 °C
Thermistor temperature (B-parameter)
182.2 °C
Result
RTD type
1 PT100=1, PT1000=2
You entered
Resistance
100 Ω
You entered

Ohms to temperature conversion is not a single formula—it depends entirely on the type of temperature sensor you’re using. For a resistance temperature detector (RTD), the most common standard is the Callendar-Van Dusen equation, while thermistors use the Steinhart-Hart equation. This page provides a working calculator for both, along with the formulas, examples, and practical guidance for converting resistance readings into temperature.

Formula

For RTDs, the simplified linear approximation is:

T = (RT / R0 − 1) / α

Where:

  • RT = measured resistance at temperature T (Ω)
  • R0 = resistance at 0°C (Ω) — typically 100 Ω for PT100, 1000 Ω for PT1000
  • α = temperature coefficient of resistance (1/°C) — 0.00385 for standard platinum (DIN EN 60751), 0.00392 for some US standards

The result T is in °C. This linear formula is accurate to about ±0.5°C over 0–100°C, but for wider ranges the Callendar-Van Dusen equation adds quadratic and cubic terms.

For thermistors (NTC type), the B-parameter equation is:

T = 1 / (1/T0 + (1/B) · ln(RT / R0)) − 273.15

Where T0 is the reference temperature in Kelvin (usually 298.15 K = 25°C), R0 is the resistance at T0 (e.g., 10 kΩ), and B is the material constant (typically 3000–5000 K).

Worked Example

Using the calculator defaults: a PT100 RTD with R0 = 100 Ω and α = 0.00385, and a measured resistance of 100 Ω. The RTD temperature is:

T = (100/100 − 1) / 0.00385 = 0 / 0.00385 = 0°C

That makes sense—at 0°C the resistance equals R0.

Now suppose the same PT100 reads 138.5 Ω. The temperature is (138.5/100 − 1)/0.00385 = (1.385 − 1)/0.00385 = 0.385/0.00385 = 100°C. This matches the standard PT100 table.

For the thermistor example, the calculator defaults use R0 = 10 kΩ at 25°C (298.15 K) and B = 3977. If the thermistor measures 10,000 Ω, the temperature is:

T = 1/(1/298.15 + (1/3977)·ln(10000/10000)) − 273.15 = 1/(1/298.15 + 0) − 273.15 = 298.15 − 273.15 = 25°C.

Why Ohms-to-Temp Conversion Matters

Resistance-based temperature sensors are everywhere—in HVAC systems, automotive engine coolant, industrial process control, and medical devices. They work because the electrical resistance of metals and semiconductors changes predictably with temperature. To interpret the reading, you must convert the raw resistance (in ohms) to a temperature value. Without the correct conversion, a sensor output of 1,000 Ω could mean 0°C for one device and 150°C for another.

How to Choose the Right Sensor and Formula

First identify the sensor type:

  • RTD (PT100, PT1000) — uses platinum, linear over a wide range, accurate from −200°C to 850°C. Use the linear formula or the Callendar-Van Dusen equation for high precision.
  • Thermistor (NTC) — high sensitivity in a narrow range (−50°C to 150°C), but highly nonlinear. Use the Steinhart-Hart equation (more accurate than the simple B-parameter) or the B-parameter equation if the datasheet only gives B.
  • Thermocouple — not a resistance sensor; it produces a voltage, so this calculator does not apply.

Check the sensor’s datasheet for its nominal resistance at 0°C or 25°C, the alpha coefficient (for RTDs), and the B value (for thermistors). The calculator above lets you adjust these to match your specific sensor.

Common Mistakes and Misconceptions

  • Using the wrong R0 — A PT100 has 100 Ω at 0°C, a PT1000 has 1000 Ω. Mixing them up gives wildly wrong temperatures.
  • Ignoring lead wire resistance — In 2-wire RTD setups, the resistance of the connecting wires adds to the measured resistance, causing errors. Use 3-wire or 4-wire configurations for accurate readings.
  • Assuming linearity for thermistors — The B-parameter equation is an approximation; for wide temperature ranges, the Steinhart-Hart equation (which includes a C coefficient) is more accurate.
  • Forgetting to convert to Kelvin — In the thermistor formula, temperatures must be in Kelvin. A common mistake is using °C directly, which yields nonsense.

Costs and Practical Considerations

RTDs are more expensive than thermistors, but they are more stable and accurate over wide ranges. A basic PT100 sensor costs a few dollars, while a precision thermistor might cost under a dollar. However, the readout circuitry also matters: RTDs require a constant current source and often an ADC, while thermistors can be used in a simple voltage divider. For most hobbyist projects, a thermistor with a 10 kΩ NTC is a low-cost choice. For industrial applications requiring traceable calibration, a PT100 with a transmitter is standard.

Safety and Accuracy Tips

  • Do not exceed the sensor’s rated temperature — platinum RTDs can handle up to 850°C, but thermistors are limited to about 150°C. Overheating may permanently damage the sensor.
  • Use proper insulation — when measuring high temperatures, ensure the sensor leads are rated for the environment to avoid shorts or fires.
  • Calibrate regularly — even platinum sensors drift over time. Use an ice bath (0°C) and boiling water (100°C at sea level) for simple checks.
  • Shield the leads — electrical noise can corrupt resistance readings. Use twisted pair or shielded cable, especially in industrial settings.

Frequently Asked Questions

Q: What is the resistance of a PT100 at 100°C?
A: According to the standard, a PT100 has 138.5 Ω at 100°C. Using the linear formula: (100/100 − 1)/0.00385 = 138.5 Ω.

Q: Can I use the same formula for a PT1000?
A: Yes, but only if you set R0 to 1000 Ω. The alpha coefficient remains the same (0.00385). The resistance at 100°C would be 1385 Ω.

Q: Why does my thermistor read 10 kΩ at room temperature?
A: That’s the nominal resistance at 25°C (R0). Many NTC thermistors are rated as “10k at 25°C.” The B value (e.g., 3977) tells you how much it changes with temperature.

Q: How accurate is the linear RTD formula?
A: For 0–100°C, the linear approximation is within ±0.5°C. Over a wider range (e.g., −50 to 250°C), errors can exceed 2°C. The Callendar-Van Dusen equation improves accuracy to ±0.1°C.

Q: What is the difference between 2-wire, 3-wire, and 4-wire RTDs?
A: The number of wires refers to how many leads connect to the sensing element. 2-wire is simplest but adds lead resistance error. 3-wire cancels lead resistance using a bridge circuit. 4-wire uses separate current and sense leads, giving the most accurate measurement.

Q: Can I convert ohms to temperature for a thermocouple?
A: No, thermocouples generate a voltage (millivolts) proportional to temperature, not a resistance change. You need a different conversion table or a thermocouple calculator.

Related

Formula used
in rtd_type | RTD type | PT100=1, PT1000=2 | 1 | 0
in r_ohm | Resistance | Ω | 100 | 0
in r0 | Nominal resistance at 0°C | Ω | 100 | 0
in a_coef | Alpha (temperature coefficient) | /°C | 0.00385 | 0
out t_rtd | RTD temperature (PT100/PT1000) | °C | (r_ohm/r0 - 1) / a_coef | 1
out t_thermistor | Thermistor temperature (B-parameter) | °C | 1/(1/298.15 + ln(r_ohm/10000)/3977) - 273.15 | 1

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation, rounded as each result states. See how the calculators work or report an error.